Stormbloc® Infiltration System Within
The Micro Drainage Program Win Des - Source Control
This
document outlines the method for sizing and checking
the size of a Stormbloc® Infiltration
System using the Micro Drainage program Win Des . This example uses
the Source Control Module but does not utilise the CASDeF feature of Win Des .
Design Criteria .
For this Example we have used the following variables:
| Return Period |
10 years |
Impermeable Area |
0.5 Ha |
M5-60 |
20 |
Infiltration Coefficient |
.01 m/hr |
Ratio R |
0.4 |
|
|
We have assumed that there is no outfall from the site and
that all of the surface water run-off must soakaway.
- Global Variables
Model the units as cellular storage with no
outflow control. An overflow can be selected if necessary,
though for this example we will not be using one.

- Rainfall
and Network Details

Enter the return period and other rainfall details as normal
- Time/Area Diagram

Enter the time area details as normal. In this instance the catchment area is
relatively small with evenly shaped characteristics, we have therefore assumed
that the time/area diagram is linear in form.
- Cellular Storage
Details
Enter the dimensions of the Stormbloc® Infiltration
System here. For this instance the Stormbloc® Infiltration
System we are looking at is 16m (20 blocks) long, 6.4m
(8 blocks) wide and 1.32 (2 blocks) deep. We therefore
input the data as a surface area, in this case 16m x
6.4m gives a surface area of 102.4m². The pond/tank
invert level should be input as the invert level of the
bottom of the blocks. The cover level is the cover level
above the infiltration system. For this example we have
used relative levels of 8 for the invert level of the
blocks and 10 for the cover level.
The infiltration coefficient should be input for the
base and/or sides. This coefficient can be calculated
from test pit results using the calculator tool shown
next to the input boxes on the left hand side of this
window. A suitable factor of safety should also be used.
The void ratio of the Stormbloc ä modules is 96%
and so a value of 0.96 should be used in the porosity
box.

The system can now be analysed by pressing the button. 
- Summary of Results
The Stormbloc® Infiltration System that we
have modelled has dimensions of 16m x 6.4m x 1.32m deep.
At a void ratio of 96% this will provide a storage capacity
of 129.76m 3 .


The summary below indicates a storage volume of 124.9m³ for the critical,
winter storm of 360 minutes. The summary also indicates that the half-drain
down time for this system will be 556 minutes, i.e. within the 24 hours required
for soakaway designs.
The proposed Stormbloc® Infiltration System will therefore
have sufficient capacity for this site.
If the volume of the infiltration system is not sufficient,
or the half drain down time is greater than 24 hours, then
adjustments can be made to the size of the infiltration
system by editing the cellular storage details.